In some circumstances the scope of the new work for such a task may be limited to the installation of a new consumer unit and new circuit protection devices. However, it may be necessary to carry out other new work in order to meet all of the required safety levels, especially if C1 conditions have been observed from an inspection of the installation.
In situations that require a consumer unit to be replaced the new consumer unit should comply with BS EN 61439-3 and Regulation 421.1.201 which requires the consumer unit to have its enclosure manufactured from non-combustible material or be enclosed in a cabinet made of non-combustible material.
Consumer units that meet the above criteria are designed to incorporate protective devices such as MCBs, RCBOs, AFDDs, and SPDs that the wiring regulations require. These devices provide much higher levels of protection & electrical safety than old fashioned fuses ever could.
Where the existing wiring is deemed to be suitable to be connected to the new consumer unit there are some specific requirements within the wiring regulations that will determine which type of protective device is required on each circuit.
Additional protection by use of 30mA RCD is required on cables buried / concealed in walls & partitions if those cables are not installed in/with earthed metallic coverings. Therefore, where the existing final circuits are installed in this way additional protection by a 30mA RCD is required, see Regulations 522.6.202, 522.6.203 & 522.6.204.
Additional protection by use of 30mA RCD is required for each circuit that passes through or serves equipment in locations containing a bath or shower, see Regulation 701.411.3.3.
Additional protection by use of a 30mA RCD is required for users of socket outlets (up to 32A rating) in all locations where they are liable to be used by persons of BA1, BA2 & BA3 capability i.e. ordinary persons, children, and disabled persons. No exceptions permitted, see Regulation 411.3.3.
AFDDs are required for single-phase AC final circuits supplying socket-outlets (up to 32A rating) in high risk residential buildings, homes in multiple occupation, care homes & student accommodation, see Regulation 421.1.7. Note: Electrium AFDDs include an integral Type A 30mA RCBO and can provide addition protection as well as arc fault protection.
SPDs should be installed in new consumer units unless the owner of the installation declares otherwise. An owner who declares that overvoltage protection is not required accepts all risks, consequences, and losses. See Regulation 443.4.1.
Catering for modern demands on an electrical installation means taking account of the connected equipment, and portable devices. These will no doubt bring DC influences and PE currents into consideration for the installer.
For example Regulation 531.3.2 requires protective conductor currents (standing earth leakage not due to a fault) to be no more than 9mA for a 30mA device to help to avoid unwanted tripping but that cannot be achieved if several circuits are protected by one RCD device.
There are also the requirements of Chapter 31 & Regulation 314.1 to consider, this requires the installer to:
Therefore, wherever additional protection by a 30mA device is required each circuit should be served by an individual Type A 30mA RCBO to fully meet the requirements of the current edition of the wiring regulations.
New work, such as the replacement of a consumer unit & associated devices should be verified in accordance with the requirements of Chapter 64 of the wiring regulations and the relevant electrical installation certificate should be given to the person ordering the work, see Regulations 641.1, 644.1 and 644.3
*Designers & installers should refer to BS7671 & other relevant documents for full requirements.
Learn more about Amendment 2 of the 18th Edition in our dedicated section here.