33kv 36kv 200A Pole Mounted Mv Polymeric Drop out Fuse Cutout
Package size per unit product 30.00cm * 25.00cm * 20.00cm Gross weight per unit product 5.000kg Description Drop-out fus
Basic Info
Model NO. | HRW-33/100 |
Breaking Capacity | High |
Type | Current Fuse |
Usage | High Voltage |
Shape | Circle |
Fusing Speed | Fast K |
Standard | IEC60282-2 |
Rated Current | 100A, 200A |
Rated Voltage | 33 Kv |
Creepage Distance | 1200mm |
Breaking Current | 6300A |
Transport Package | Export Standard Package or as Client Requirement |
Specification | ISO9001: 2015 |
Trademark | L&R |
Origin | Wenzhou, Zhejiang |
Production Capacity | 20, 000PCS/Month |
Packaging & Delivery
Package size per unit product 30.00cm * 25.00cm * 20.00cm Gross weight per unit product 5.000kgProduct Description
DescriptionDrop-out fused cut out and load Switching fuse cutout are of outdoor used high voltage protective device.To be connected with incoming feeder of distribution line it mainly protect transformer or lines from shortcircuit and overload, and on/off loading current.Standard: IEC 60282-2
Components
Drop-out fused cut out is composed of insulator supports and fuse tube. Static contacts is fixed on insulator support and moving contact is installed on two ends of fuse tube. Fuse tube is composed of:1. Inside arc estinguishing tube2. Outer phenolic compound paper tube or epoxy glass tubeLoad switching fuse cutout provides enforced elastic auxiliary contacts and arc-extinguishing enclosure for switching on/off loading current.
Operating Principle
1. When working normally, fuse link tightened the fuse tube to be close position.2. If system occur faults, big fault current melts fuse immediately and take place electric arc, which makesarc extinguishing tube being heated and explode a lot of gases. This will produce high pressure and blow off the arc along with tube.3. After fuselink melt moving contact has no tightened strength, mechanism is locked and fuse tube dropout.4. Cutout now is in open position. Operator shall use insulating Link Rod to pull the moving contact.
Main Parameter
Type | Rated Voltage (kV) | Rated Current (A) | Breaking Current (A) | Impulse Voltage Bil (BIL) | Power Frequency withstand voltage | Leakage Distance (mm) | Weight (kg) | Dimension (cm) |
HRW-12 | 12 | 100 | 6300 | 110 | 40 | 250 | 6 | 40X36X11.5 |
HRW-12 | 12 | 200 | 10000 | 110 | 40 | 250 | 6 |
Type | Rated Voltage (kV) | Rated Current (A) | Breaking Current (A) | Impulse Voltage Bil (BIL) | Power Frequency withstand voltage | Leakage Distance (mm) | Weight (kg) | Dimension (cm) |
HRW-33 | 33 | 100 | 10000 | 170 | 70 | 850 | 12 | 90X40X17 |
HRW-33 | 33 | 200 | 12500 | 170 | 70 | 850 | 12 |