Category
3 Pole Withdrawable Type Vacuum Interrupter
Withdrawable circuit-breakers Description VD4 series medium voltage vacuum circuit-breakers with lateral operating mecha
Basic Info
Model NO. | VD4 |
Breaking Capacity | High Voltage Circuit Breakers |
Operation | Electric Type |
Speed | Normal Type Circuit Breaker |
Arc-extinguishing Medium | Vacuum |
Installation | Fixed/Drawable |
Structure | Vcb |
Poles Number | 3 |
Type | Circuit Breaker |
Function | Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection |
Certification | ISO9001-2000 |
Transport Package | Carton |
Specification | IEC, GB |
Trademark | Rockwill |
Origin | China |
HS Code | 8535210000 |
Production Capacity | 1000PCS |
Product Description
Withdrawable circuit-breakers
Description
VD4 series medium voltage vacuum circuit-breakers with lateral operating mechanism feature the separate pole construction technique.The operating mechanism is the EL trip-free stored energy type with independent opening and closing regardless of the operator's action. The EL operating mechanism is widely used in all VD4 series circuit-breakers with frontal control.The circuit-breaker can be remote controlled when fitted with dedicated electrical accessories (gearmotor, opening and closing release).The operating mechanism, the three poles and the current sensors (if installed) are assembled on a metal frame without wheels. The construction is extremely compact, strongly built and low in weight. VD4 series circuit-breakers with lateral operating mechanisms are life-long sealed pressure devices (Standards IEC 62271-100 and CEI EN 62271-100). Additionally, VD4 series circuit-breakers have been type tested for low temperature and marine applications (Germanischer Lloyd).VD4 vacuum circuit breakers have been designed for indoor use and air insulated switchboards.
Advantages
Vacuum circuit-breakers have particular advantages for use in networks where there is a high switching frequency in the working current range and/ or where a certain number of short- circuit breaking operations are expected. VD4 vacuum circuit- breakers are suitable for auto reclosing and have exceptionally high operating reliability and long life. The circuit- breakers are notable for their compact design, small dimensions together with high capacity. The operating mechanisms have a low maintenance requirement and the interrupters are maintenance- free throughout their service lives. They are well suited to all load breaking operations which occur in practice, and in particular:
- Short-circuit currents;
- Overhead lines under load and, no-load conditions;
- Cables under load and no-load conditions;
- Transformers under load and no-load conditions;
- Generators under load and no-load conditions;
- Ripple control system;
- Capacitor banks(also parallel switching) and Motors with starting currents above 600A;
Fields of application
Below is the list of SM6 range units used in MV/LV transformer substations and industrial distribution substations:
- Cable control and protection
- Overhead control and protection
- Transformers and distribution substations
- Motor and transformer control and protection
- Generator control and protection
- Capacitor bank control and protection
Diagrammatic sketch
Circuit-breaker operating mechanism
A Open/closed auxiliary contactsB Geared motor for closing spring chargingC Built-in closing spring charging leverD Mechanical signalling device for circuit-breaker open/closedE Mechanical operation counterF Plug-socket connectors of electrical accessories in the truckG Signalling device for closing springs charged/discharged | H Service releasesI Closing pushbuttonL Opening pushbuttonM Operating mechanism locking electromagnetN Additional shunt opening releaseO Transient contactP Contacts for signalling spring charged/discharged |
Main characteristics
Circuit-breaker | VD4/W 36 | |
Standards | IEC 62271-100 | |
Rated voltage | Ur [kV] | 36 |
Rated insulation voltage | Us [kV] | 36 |
Withstand voltage at 50 Hz | Ud (1 min) [kV] | 70 |
Impulse withstand voltage | Up [kV] | 170 |
Rated frequency | fr [Hz] | 50 |
Rated normal current | Ir [A] | 630 / 1250 / 1600 / 2000 / 2500 / 3150 |
Rated breaking capacity (rated short-circuit breaking current symmetrical) | Isc [kA] | 20 / 25 / 31.5 / 40 |
Rated short-time withstand current (3s) | Ik [kA] | 20 / 25 / 31.5 |
Making capacity | Ip [kA] | 50 / 63 / 80 / 100 / 125 |
Operation sequence | [O - 0.3 s - CO - 15 s - CO] | |
Opening time | [ms] | 33 ~ 60 |
Arcing time | [ms] | 10 ~ 15 |
Total breaking time | [ms] | 43 ~ 75 |
Closing time | [ms] | 30 ~ 60 |
Operating temperature | [ºC] | -5 ~ + 40 |