Category
Flrn36-12 Convenient Installation AC High-Voltage Load Break Switch Lbs
Jiangsu Dechu Power Electric CO.,LTD Our company has ten years of experience in manufacturing electrical equipment, has
Basic Info
Model NO. | FLRN36-12 |
Transport Package | in Wooden |
Trademark | DECHUN |
Origin | Changzhou, Jiangsu, China |
HS Code | 85389000 |
Product Description
Jiangsu Dechu Power Electric CO.,LTDOur company has ten years of experience in manufacturing electrical equipment, has a research and development team, and has independent research and development capabilities. Our customers are located in more than a dozen countries.The customer came to my factory to check the order.
PRODUCT SPECIFICATION:
Item | Unit | Parameter | |
FLN36-12D/T630-20 | FLN36-12D/T125-31.5 | ||
Rated voltage | KV | 12 | 12 |
Rated frequency | Hz | 50 | 50 |
Rated current | A | 630 | 630 |
1 min power frequency withstand voltage | KV | 42/48 | 42/48 |
Lighting impulse withstand voltage | KV | 75/85 | 75/85 |
5 min zero gauge rated power frequency withstand voltage | KV | 24 | 24 |
Rated thermal stability current(peak) | KA | 20/20 | |
Rated dynamic current(peak) | KA | 50/50 | |
Rated short circuit closing current | KA | 50/50 | |
Rated closed-loop breaking current | A | 630 | |
Rated active load breaking current | A | 630 | |
Rated cable charging breaking current | A | 10 | 10 |
Rated short circuit breaking current | KA | 31.5 | |
Rated transfer current | A | 1750 | |
Fuse type | XRNT-12KV/125A | ||
Fuse strikes the output energy | J | 1±0.5 | |
Mechanical life | Time | 5000/2000 | 5000/3000 |
The insulation distance betweent the live body and the ground | mm | >=125 | >=125 |
SF6 Gas pressure (relative pressure at 20ºC) | bar | 0.4 | 0.4 |
Closing the same period | ms | <=2 | <=2 |
Main circuit tesistance | μΩ | <=65 | <=65 |
PRODUCTION DESCRIPTION:
FLRN36-12 indoor AC high-voltage SF6 load break switch is an indoor switch equipment with 12kV rated voltage. The equipment adopts SF6 as gas arcing and insulation medium, including three phases which are opening , closing and earthing, It has the advantages of small volume, convenient installation and strong adaptability to the environmental.