Category
High Voltage Outdoor Pole Mounted Disconnect Switch Load Break Switch Earth Switch Ground Switch
Package size per unit product 80.00cm * 40.00cm * 50.00cm Gross weight per unit product 120.000kg High Voltage Outdoor P
Basic Info
Model NO. | GW9-12 |
Type | High-voltage |
Structure | Three-column Disconnector |
Installation | Outdoor High-voltage |
Operation | Electric |
Grounding Mode | Grounding |
Movement Mode | Vertical Rotary Type |
Number of Poles | Three Pole |
Grounding | Single Ground |
Series | Three |
Run | Vertical Rotation |
Switching Mode | Single Throw-in |
Common Model | YR |
Structure of Operating | Electric |
Certification | ISO, ISO9001 |
Brand | Nce |
Transport Package | Plywood Box |
Specification | 750*450*200mm |
Trademark | NCE |
Origin | China |
HS Code | 8535309000 |
Production Capacity | 3000set/Month |
Packaging & Delivery
Package size per unit product 80.00cm * 40.00cm * 50.00cm Gross weight per unit product 120.000kgProduct Description
High Voltage Outdoor Pole Mounted Disconnect Switch Load Break Switch Earth Switch Ground SwitchWorking conditionName | Unit | Applicable condition | |
Ambient air temperature | Max temperature | ºC | +50 |
Min temperature | -60 | ||
Max daily temperature difference | K | 30 | |
Altitude | m | ≤3000 | |
Solar radiation intensity | W/cm2 | 0.1 | |
Pollution degree | IV | ||
Icing thickness | mm | 10 | |
Humidity | Daily relative humidity average | % | ≤100 |
Monthly relative humidity average | ≤95 | ||
Earthquake tolerance ability | degree | ≤8 |
Item | Unit | Data | ||
Rated voltage | kV | 12 | ||
Rated current | A | 630 | ||
Rated frequency | Hz | 50/60 | ||
Rated peak withstand current | kA | 50 | ||
Rated short time withstand current | kA | 20 | ||
Rated short circuit duration | S | 4 | ||
Rated active load breaking current | A | 630 | ||
Rated circuit breaking current | A | 630 | ||
Rated cable charging current | A | 10 | ||
5% rated active load breaking current | A | 31.5 | ||
Rated power transformer breaking current | A | 1250 | ||
Rated short-circuit making current | kA | 50 | ||
Main circuit resistance | μΩ | <90 | ||
1min power frequency withstand voltage | Dry | phase to phase, to earth | kV | 42 |
across open contacts | 49 | |||
Wet | phase to phase, to earth | 30 | ||
Lightning impulse withstand voltage (peak) | phase to phase, to earth | kV | 75 | |
across open contacts | 85 | |||
Mechanical life | times | 2000 |