Basic Info
Model NO. | VSG1-12 |
Poles Number | 3 Pole |
Type | Circuit Breaker |
Function | Short-Circuit |
Certification | ISO9001-2000, CCC |
Transport Package | Plywood |
Trademark | Talent |
Origin | China |
HS Code | 8535210000 |
Production Capacity | 5000 Pieces/Year |
Product Description
VSG1-12 Vacuum Circuit Breaker, Indoor type
1.General1.1 Ratings:rated voltage 12KV, rated current 630A~1250A, AC50HZ1.2 Application: for the control and protection of substation and equipments; making and breaking short-circuit current under various operating status of electric network.1.3 Standard: IEC62271-1002. Type and Interpretation3. Working condition3.1 Ambient air temperature: -25~40ºC3.2 Altitude:≤2000m3.3 No operating in such as subject to dust, dirt, smog, corrosive/flammable gas, vapor and salt pollution.3.4 Humidity: Daily average value ≤95% Monthly average value ≤90%3.5 Water vapor pressure: Daily average value ≤2.2Kpa3.6 The external shocking and earthquake could be neglected.3.7 The amplitude of electromagnetic interference in the secondary system ≤1.6KVNote: Customized products are available on your requirements.4.Main technical parameter
Item | Unit | Data |
Rated voltage | KV | 12 |
Rated 1min power frequency withstand voltage(vacuum open contacts)insulation Lightening impulse withstand voltage(vacuum open contacts)level | KVKV | 4275 |
Rated frequency | HZ | 50 |
Rated current | A | 630,1250 |
Rated short-time withstan current | KA | 16,20,25, 31.5 |
Rated withstand current(peak) | KA | 40,50,63 |
Rated short-circuit breaking current | KA | 16,20,25 |
Rated short-circuit making current | KA | 40,50,63 |
Rated duration of short-circuit | S | 4 |
Rated operating sequence | | O-0.3S-CO-180S-CO |
Mechanical life | | M2 class(30000times) |
Rated voltage of operating power | | AC 220/DC 220 |
Full breaking time | | ≤70 |
Electrical life | | E2 class |
5.Overall and Installation Dimension5.1 overall and installation dimension of fixed type circuit breaker
Alternative parameters table1
Rated voltage | Rated current | Rated short-circuit | P | A | B | D |
KV | KA | breaking current, KA | mm | mm | mm | mm |
12 | 630,1250 | 20,25,31.5 | 150 | 20 | 410 | 450 |
Alternative parameters table2
Rated voltage | Rated current | Rated short-circuit | P | A | B | C | D | W |
KV | KA | Breaking current, kA | mm | mm | mm | mm | mm | mm |
| 630 | 20,25 | | | | | | 35 |
12 | 630,1250 | 20,25,31.5,40 | 150 | 494 | 456 | 490 | 502 | 49 |
Series Number | Symbol | Name | Remark |
1 | YQ-Y9 | Indirect over-current release | Chosen element |
2 | Y1-Y4 | Rectifier element | |
3 | KO | Inner mechanism anti-jumping relay | |
4 | P | Handle operation mechanism | |
5 | Y1 | blocking eletromagnet | Chosen element |
6 | HQ | Closing release | |
7 | TQ | Breaking release | |
8 | M | Energy storing engine | |
9 | S9 | assistant switch used at operation position | |
10 | S8 | assistant switch used, at test positin | Chosen element |
11 | S2 | Blocking electromagnet assistant switch | |
12 | S1 | Inching switch for energy storing | |
13 | QF | assistant switch of breaker contact | |