6/10kv 12/20kv 18/30kv Mv Underground Power Cables Outdoor Energy IEC 60502 BS 6622 6.35/11kv 12.7/22kv 19/33kv Swa Cable
Basic Info
Model NO. | YJV32 YJV22 |
Application | Construction, Overhead, Underground, Industrial, Power Station |
Voltage | Medium Voltage Cable |
Current | DC & AC |
Insulation Material | XLPE |
Sheath Material | PVC |
Material Shape | Round Wire |
Wire Core Material | Bare Copper Wire |
Certification | ISO, CCC, CE, RoHS, TUV |
Model | Yjv32 |
Brand | Qifan |
Plant No. | 3 Plant with 12 Workshop |
Engineer No. | 206 |
Free Sample | Yes |
Staff | 3048 |
QC | 208 |
Standard | IEC VDE BS AS/NZS Icea Sans |
Transport Package | Drum |
Specification | 25-1600mm2 |
Trademark | QIFAN |
Origin | China |
HS Code | 8544601200 |
Production Capacity | 500km/Month |
Product Description
MV Underground Power Cables Outdoor Energy IEC 60502 BS6622- 6/10 6.35/11kV6/10kV 12/20kV 18/30kV MV Underground Power Cables Outdoor Energy IEC 60502 BS 6622 6.35/11kV 12.7/22kV 19/33kV SWA CableMV Underground Power Cables Outdoor Energy BS 7835 - 6.35/11kV SWAApplication
Their aluminium wire armour (AWA) for single core cables and steel wire armour (SWA) for multicore cables provide robust mechanical protection making these MV cables suitable for direct burial in the ground. These armoured MV mains power cables are more commonly supplied with copper conductors but they are also available with aluminium conductors upon request to the same standard. The copper conductors are stranded (Class 2) whereas the aluminium conductors are compliant to the standard using both stranded and solid (Class 1) constructions.
Operating characteristics
1. Laying temperature: ≥0°C;
2. Cable conductor long-term allowable working temperature: PVC insulated ≤70°C, XLPE insulated ≤90°C;
3. Maximum operating temperature in case of short-circuit: PVC insulated ≤160°C, XLPE insulation ≤ 250°C;
4. Cable bending radius:
Item | Single-core | Three-core | ||
Non-armored | Armored | Non-armored | Armored | |
Installation | 20D | 15D | 15D | 12D |
Close to the terminal and connection box | 15D | 12D | 12D | 10D |
Note: D is the cable diameter
MV Cables Construction
BS6622 | BS7835 | |
---|---|---|
Conductor | Class 2 stranded copper or Class 1 solid /Class 2 stranded aluminium | |
Conductor Screen | Semi-conductive Cross-Linked Polyethylene (XLPE) | |
Insulation | XLPE | |
Insulation Screen | Semi-conductive XLPE | |
Metallic Screen | Individual or overall copper tape | |
Filler | Polyethylene Terephthalate (PET) fibres | |
Separator | Binding Tape | |
Bedding | Polyvinyl Chloride (PVC) | Low Smoke Zero Halogen (LSZH) compound |
Armour | Single core cable: Aluminium Wire Armour (AWA)Multicore cable: Steel Wire Armour (SWA) | |
Sheath | PVC or Medium Density Polyethylene (MDPE) | LSZH |
Cable models, names, and laying conditions
Model | Name | Laying Occasion | |
Copper core | Aluminum core | ||
YJV | YJLV | XLPE insulated PVC sheathed power cable | Laid indoors, and in tunnels and pipelines |
YJY | YJLY | XLPE insulated PE sheathed power cable | |
YJV22 | YJLV22 | XLPE insulated steel tape armored PVC sheathed power cable | Adapt for buried laying, not suitable for in-pipe laying |
YJV23 | YJLV23 | XLPE insulated steel tape armored PE sheathed power cable | |
YJV32 | YJLV32 | XLPE insulated thin steel wire armored PVC sheathed power cable | Laid on riverbeds of rivers or shallow water as connecting lines across rivers or petroleum/natural gas platforms, also used in land high drop areas. |
YJV33 | YJLV33 | XLPE insulated thin steel wire armored PVC sheathed power cable | |
YJV42 | YJLV42 | XLPE insulated thick steel wire armored PVC sheathed power cable | |
YJV43 | YJLV43 | XLPE insulated thick steel wire armored PE sheathed power cable |
Armoured 3-core cable with XLPE insualtion. Rated voltage 6/10 KV 6.35/11KV
Cable Data
Conductor | Insulation thickness (mm) | Copper tape screen (approximate) (mm) | PVC bedding thickness (mm) | Armored wire outer diameter (mm) | Sheath thickness (mm) | Outer diameter (approximate) (mm) | Copper core cable weight (kg/km) | Aluminum core cable weight (kg/km) | ||
Cross sectional area (mm2) | Structure | Outer diameter (mm) | ||||||||
25 | Compact round | 6.0 | 3.4 | 0.1 | 1.3 | 2.5 | 2.5 | 48.0 | 4175 | 3703 |
35 | Compact round | 7.2 | 3.4 | 0.1 | 1.3 | 2.5 | 2.6 | 50.8 | 4733 | 4072 |
50 | Compact round | 8.4 | 3.4 | 0.1 | 1.4 | 2.5 | 2.7 | 53.8 | 5491 | 4547 |
70 | Compact round | 10.0 | 3.4 | 0.1 | 1.5 | 2.5 | 2.8 | 57.6 | 6446 | 5124 |
95 | Compact round | 11.7 | 3.4 | 0.1 | 1.5 | 2.5 | 2.9 | 61.5 | 7530 | 5737 |
120 | Compact round | 13.1 | 3.4 | 0.1 | 1.6 | 2.5 | 3.0 | 64.9 | 8628 | 6363 |
150 | Compact round | 14.6 | 3.4 | 0.1 | 1.6 | 2.5 | 3.1 | 68.3 | 9794 | 6963 |
185 | Compact round | 16.3 | 3.4 | 0.1 | 1.7 | 2.5 | 3.3 | 72.6 | 11326 | 7834 |
240 | Compact round | 18.5 | 3.4 | 0.1 | 1.8 | 3.15 | 3.5 | 79.2 | 14268 | 9737 |
300 | Compact round | 20.7 | 3.4 | 0.1 | 1.9 | 3.15 | 3.6 | 84.8 | 16641 | 10978 |
400 | Compact round | 23.8 | 3.4 | 0.1 | 2.0 | 3.15 | 3.9 | 92.3 | 20362 | 12811 |
500 | Compact round | 26.6 | 3.4 | 0.1 | 2.1 | 3.15 | 4.1 | 99.3 | 24203 | 14764 |
Note: The single-core armored cables are used for the D.C. system only. If used for the A.C. system, the magnetic isolation should be applied to the steel armor wires of non-magnetical materials that should be used.
3 Operating characteristics- Rated power-frepuency voltage U0/U: 6.35/11kV.
- Max.admissible operating temperature of the conductor:90ºC.
- Max. short-circurt temperature of conductor shall not exceed 250ºC. (5s maximum duration)
- The ambient temperature under installation should not below 0ºC.
- The bending radius of a single-core cable should not less than 20 times of the cable diameter.
The bending radius of a multi-core cable should not less than 15 times of the cable diameter.