Medium Voltage 12kv, 2500A, 40ka Circuit Breaker Embedded Poles, Vacuum Arc Extinguishing Chamber Embedded Pole
Basic Info
Model NO. | VEP358A |
Breaking Capacity | High Voltage Circuit Breakers |
Operation | Electric Type |
Speed | Normal Type Circuit Breaker |
Arc-extinguishing Medium | Vacuum |
Installation | Fixed |
Structure | Contactor |
Poles Number | 3 |
Type | Circuit Breaker |
Function | Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection) |
Certification | ISO9001-2000 |
Transport Package | Cartons/Pallets |
Trademark | Feite Brand |
Origin | China |
HS Code | 8535900090 |
Production Capacity | 60000/Year |
Product Description
Vacuum arc extinguishing chamber embedded pole
The epoxy solid sealing pole (also known as the solid seal type vacuum arc extinguishing chamber) is a buffer material outside the vacuum switch tube and then a layer of epoxy resin. It replaces the insulation support and mechanical support of the original circuit breaker, greatly reducing the circuit breaker's parts and volume. With small size, more stable and reliable pressure advantages it realizes the integrated module, and more easy for installation and free-maintenance.
Wuhan Feite brand solid sealed pole of the epoxy resin automatic pressure gel forming process (APG process) the vacuum arc quenching chamber and an upper and a lower outlet seat and current carrying components are encapsulated into a whole. Due to the adoption of the excellent performance epoxy resin material, greatly ensure the products' mechanical, electrical and thermal aging performance, The embedded pole has good vacuum sealing performance. It is reliable and with good resistance to high and low temperature shock and mechanical shock resistance. It has the advantage of maintenance free, compact, easy to install. Epoxy solid sealed pole matching the corresponding indoor and outdoor vacuum circuit breaker or a vacuum distribution device, especially matching in frequency is 50Hz / 60Hz, rated voltage of 12kV, 17.5kV, 24kV, 27.5 kV and 40.5 kV electric power, machinery, chemical industry, metallurgy, mining and other departments operating condition operating frequently places.
Embedded poles for 12KV circuit breaker; VEP358A; VEP2500/12-40
Main Technical Data
ELECTRICAL RATINGS(3PHASE) SYMMETRICAL BASIS | |
1.Rated Voltage | 12KV |
2.Rated Current | 2500A |
3.Rated Frequency | 50/60Hz |
4.Rated Short-circuit Breaking Current | 40KA |
5.Rated Operations of Short-circuit Breaking Current Interruption | 30times |
6.Rated Short-circuit Making Current | 100ka |
7.Rated Short-time Withstand current(4s) | 40KA |
8.Rated Single Capacitor Bank Breaking Current* | 630A |
9.Rated back-to-back capacitor bank breaking current* | 400A |
10.Short-time(1min) power-frequency withstand voltage | 48KV |
11.Rated Lighting impulse withstand voltage(peak) | 85KV |
12.Circuit resistance at rated contact force | ≤18μΩ |
13.Mechanical Life | 20,000times |
14.Contact Closing Force due to Bellow and Atmospheric | 210±50N |
15.Counterforce at rated contact force | 250±50N |
16. Contact Erosion Limit | 3mm |
17.Shelf Life | 20Years |
18.Part discharge | ≤5pc |
19.Rate operating sequence | O-0.3s-CO-180s-CO |
MECHANICAL REQUIREMENTS(REF. VCB) | |
1.Contact Stroke | 9±1 mm |
2.Contact connection stroke | 4±1 mm |
3.Average opening speed | 1.1±0.2m/Sec |
4.Average closing speed | 0.6±0.2m/Sec |
5.Added contact force | 4200±300N |
6.Bounce duration of contact closing | ≤2ms |
7.Out of simultaneity of contact closing and opening | ≤1ms |
8.Max.overtravel | ≤2mm |
Notes: 1.Meets or exceeds the electrical endurance requirements of class E2 for auto reclosing duty per IEC 62271-100 and GB 8738-2003.2.* Rated Characteristics to be given on request |
1> Vacuum Interrupter Components
2> Vacuum Interrupter Production Equipments
3> Different Types Vacuum Interrupter and Embedded Poles
4> Honors
5> Vacuum Interrupter and Embedded Poles Stock
6> Company Introduction