Category
Solar Disconnector Switch 1500V 400A 630A 800A 2p Load Break Switch
Solar Disconnector Switch 1500V 400A 630A 800A 2p Load Break Switch DC load Isolator Switch with IEC standard,Available
Basic Info
Model NO. | EHDT |
Type | Low-voltage |
Structure | Single-column Disconnector |
Installation | Indoor High-voltage |
Operation | Manual |
Grounding Mode | Grounding |
Movement Mode | Plug-in Type |
Number of Poles | Three Pole |
Grounding | Single Ground |
Series | Single-Stage |
Run | Turn the Horizontal |
Switching Mode | Single Throw-in |
Common Model | YR |
Structure of Operating | Electric |
Certification | ISO, GS, RoHS, CE, IS9001, ISO9001, ISO9002, ISO2000 |
Brand | Onccy |
Transport Package | Box |
Specification | plastic |
Trademark | Onccy |
Origin | China |
Product Description
Solar Disconnector Switch 1500V 400A 630A 800A 2p Load Break SwitchDC load Isolator Switch with IEC standard,Available from 400A-630A-800A in 4P version, acting as a load break switches for DC current. Especially indicated for installations for photovoltaic energy generators, which require a safe disconnection. Standard handle is supplied pad lockable in position "OFF" for maintenance. Bridging links available for series connections.
Product Benefits
Easy to install
- Wiring: Since the switch is non-polarized, all types of wiring and connections are possible.
- Easy access without tools, and auxiliary contacts can be integrated without tools.
- The mechanical device can be centered to meet the installation requirements.
Safe reliable operation
- Reliable position indication through visible contacts.
- The opening and closing of the switch is fully independent from the speed of operation, ensuring safe operation under all conditions.
- High temperature withstand: no derating up to 55 C(131F),functional from -40 to+122F(-40 to +50°C).
Designed for harsh environments
- Vibration testing (from 13.2 to 100 Hz at 0.7 g).
- Choc testing (15 g during three cycles).
- Humid temperature testing (2 cycles, 55C/131F with 95% humidity level).
- Salt mist testing(3 cycles with humidity storage, 40C/104F, 93% humidity after each cycle).
Technical Data
Rated current Ie | 160A | 250A | 315A | 315H | 400A | 630A | 800A | ||||
Frame size | EHD-315 | EHD-630 | |||||||||
Thermal current (Ith) | 160 | 250 | 315 | 400 | 400 | 630 | 800 | ||||
Rated insulation voltage (Ui) | 1500 | 1500 | 1500 | 1500 | 1500 | 1500 | 1500 | ||||
Rated impulse withstand voltage Uimp (KV) | 12 | 12 | 12 | 12 | 12 | 12 | 12 | ||||
Code | Number of poles | Rated voltage | Utilisation category | Ie(A) | Ie(A) | Ie(A) | Ie(A) | Ie(A) | Ie(A) | Ie(A) | |
EHDN | 2P(1P+,1P-) | 4P(2P+,2P-) | 1000VDC | DC-PV1/DC-21B | 160 | 250 | 315 | 400 | 400 | 630 | 800 |
EHDT | 2P(1P+,1P-) | 4P(2P+,2P-) | 1500VDC | DC-PV1/DC-21B | 100 | 160 | 250 | 315 | 400 | 630 | 800 |
EHDT | 3P(2P+,1P-) | 6P(4P+,2P-) | 1500VDC | DC-PV1/DC-21B | - | - | 315 | 400 | - | - | - |
Number of poles | Rated voltage | Utilisation category | Ie(A) | Ie(A) | Ie(A) | Ie(A) | Ie(A) | Ie(A) | Ie(A) | ||
EHDN | 2P(1P+,1P-) | 4P(2P+,2P-) | 1000VDC | DC-PV2 | 160 | 250 | 315 | - | 400 | 630 | - |
EHDT | 2P(1P+,1P-) | 4P(2P+,2P-) | 1500VDC | DC-PV2 | 100 | 160 | 250 | - | 400 | 630 | - |
EHDT | 3P(2P+,1P-) | 6P(4P+,2P-) | 1500VDC | DC-PV2 | - | - | 315 | - | - | - | - |
The short-circuit capacity is between 1000 and 1500VDC (no protection) | |||||||||||
Rated short time withstand current lcw 1s (kAeff) Icw | 5 | 5 | 5 | 5 | 8 | 8 | 8 | ||||
Rated short-circuit making capacity lcm(kA peak)- 60 ms Icm | 10 | 10 | 10 | 10 | 10 | 10 | 10 | ||||
Cable | |||||||||||
Recommended Cu rigid cable cross section(mm) | 70 | 120 | 185 | 185 | 240 | 2×185 | 2×240 | ||||
Recommended Cu busbar width(mm) | 20 | 20 | 20 | 20 | 25 | 25 | 25 | ||||
Mechanical characteristics | |||||||||||
Durability (number of operating cycles) | 8000 | 8000 | 8000 | 8000 | 8000 | 8000 | 8000 | ||||
Number of cycles of operation with current | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 |
Q: Are you trading company or manufacturer ?
A: We are manufacturer. We have 30,000 square meters of self-owned plant
Q: Do you have any certificates?
A: Yes,we have UL, TUV, CB, SAA, CCC, CE and other certifications
Q: How do we make a quick response to customer , 5 inquiry ?
A: Our professional team will reply you online or by email,Skype, whatsApp and so on
Q: Do you have any exporting experience?Which countries did you export to before?
A: We have lots of exporting experience and customers in many countries,such as America, Japan,Australia,UAE,Canada,Vietnam,Turkey,Thailand,Russia,UK,etc
Q:Can you supply samples for checking ?
A: Yes, we can supply samples, pls contact for detailed required
Q:How long is your delivery time?
A: Generally it is within 3days for small qty. Or it is around 15-20 days to a general order
Q: What is the standard of package of your goods?
A: Export standard package or special package according to customer requirement
Q:How about inspection?
A: We have the whole inspection system from raw material to end products include transient test, delay test,mechanical life test and so on
Q:What is the service offered by company?
A: We have the professional engineer team which can design and develop the mould to arrive different customer requirements. We also have the professional sales team to offer good service from pre-sale to after-sale.